[Products]

ENERGIN® CHP Units

Maximum energy utilisation for combined heat and power.

ENERGIN® CHP units generate electricity while recovering heat from both the engine jacket water and exhaust gases, delivering outstanding overall efficiency.
Powered by Enertec’s in-house M-series engines, they operate on a wide range of gaseous fuels, including natural gas, biogas, LPG, wood gas and flare gas.

[About]

Technical Specifications

Electrical output

115–500 kW

Scalable output

Up to 50 MW

Overall efficiency

Up to 91.6%

Key Benefits

Maximum heat recovery from jacket water and exhaust gases

High overall efficiency of up to 91.6%

Compact, factory-assembled design for easy installation

Optional soundproof enclosure (<35 dB(A))

[Options]

Unit Type

Configuration Solution type Fuel type Grid frequency Electrical power / kW Electrical efficiency / % Thermal power / kW Overall efficiency / %
M06 CHP P115 CHP LPG / Propane 50 Hz 115 30.7 225 90.7
M06 CHP H122 CHP Woodgas 50 Hz 122 34.8 182 86.7
M06 CHP G140 CHP Natural Gas 50 Hz 140 38.6 187 90.1
M06 CHP B140 CHP Biogas 50 Hz 140 39.3 165 85.6
M08 CHP H166 CHP Woodgas 50 Hz 166 34.9 248 87.0
M06 CHP P173 CHP LPG / Propane 50 Hz 173 34.9 277 90.9
M06 CHP G200 CHP Natural Gas 50 Hz 200 41.0 241 90.4
M06 CHP B200 CHP Biogas 50 Hz 200 41.8 213 86.3
M06 CHP P205 CHP LPG / Propane 50 Hz 205 35.8 301 88.3
M08 CHP P233 CHP LPG / Propane 50 Hz 233 35.0 375 91.3
M06 CHP G250 CHP Natural Gas 50 Hz 250 41.8 272 87.3
M06 CHP B250 CHP Biogas 50 Hz 250 42.6 238 83.1
M12 CHP H250 CHP Woodgas 50 Hz 250 35.0 375 87.4
M08 CHP G260 CHP Natural Gas 50 Hz 260 41.0 315 90.7
M08 CHP B260 CHP Biogas 50 Hz 260 41.7 280 86.6
M08 CHP P260 CHP LPG / Propane 50 Hz 260 35.9 382 88.6
M08 CHP G333 CHP Natural Gas 50 Hz 333 41.9 364 87.7
M08 CHP B333 CHP Biogas 50 Hz 333 42.6 320 83.6
M12 CHP P350 CHP LPG / Propane 50 Hz 350 35.1 561 91.4
M12 CHP G400 CHP Natural Gas 50 Hz 400 41.1 483 90.7
M12 CHP B400 CHP Biogas 50 Hz 400 41.9 427 86.6
M12 CHP P450 CHP LPG / Propane 50 Hz 450 36.0 657 88.5
M12 CHP G500 CHP Natural Gas 50 Hz 500 42.1 539 87.5
M12 CHP B500 CHP Biogas 50 Hz 500 42.7 477 83.5
CHP P130/60 Hz CHP LPG / Propane 60 Hz 130 31.0 250 90.7
CHP H140/60 Hz CHP Woodgas 60 Hz 140 33.3 226 87.0
CHP G150/60 Hz CHP Natural Gas 60 Hz 150 37.0 215 90.1
CHP B150/60 Hz CHP Biogas 60 Hz 150 37.8 192 86.2
CHP P173/60 Hz CHP LPG / Propane 60 Hz 173 33.5 298 91.1
CHP H180/60 Hz CHP Woodgas 60 Hz 180 33.4 289 87.0
CHP P205/60 Hz CHP LPG / Propane 60 Hz 205 34.3 325 88.6
CHP G210/60 Hz CHP Natural Gas 60 Hz 210 39.5 272 90.6
CHP B210/60 Hz CHP Biogas 60 Hz 210 40.2 242 86.6
CHP P233/60 Hz CHP LPG / Propane 60 Hz 233 33.5 402 91.3
CHP G250/60 Hz CHP Natural Gas 60 Hz 250 40.3 294 87.7
CHP B250/60 Hz CHP Biogas 60 Hz 250 41.1 258 83.5
CHP P260/60 Hz CHP LPG / Propane 60 Hz 260 34.3 411 88.6
CHP H275/60 Hz CHP Woodgas 60 Hz 275 33.5 446 87.8
CHP G280/60 Hz CHP Natural Gas 60 Hz 280 39.5 364 90.8
CHP B280/60 Hz CHP Biogas 60 Hz 280 40.2 324 86.8
CHP G333/60 Hz CHP Natural Gas 60 Hz 333 40.4 393 88.0
CHP B333/60 Hz CHP Biogas 60 Hz 333 41.2 345 83.8
CHP P350/60 Hz CHP LPG / Propane 60 Hz 350 33.6 604 91.6
CHP G420/60 Hz CHP Natural Gas 60 Hz 420 39.6 546 91.1
CHP B420/60 Hz CHP Biogas 60 Hz 420 40.4 485 87.0
CHP P450/60 Hz CHP LPG / Propane 60 Hz 450 34.5 708 88.8
CHP G500/60 Hz CHP Natural Gas 60 Hz 500 40.5 584 87.8
CHP B500/60 Hz CHP Biogas 60 Hz 500 41.2 513 83.5

Do You Need
a Consultation?

Fill out the form, and our specialist will contact you and answer all your questions.

e.g. type of fuel, required power, project location, planned operating hours per year

Your details are used only to process your request. By submitting this form, you confirm that you have read and agree to our Privacy Policy.

Find your ENERGIN®

Step 1 of 5

Which fuel will you run on?

Determines the engine series and gas train.

Prefer to write to us directly? Contact us